Thông số kỹ thuật:
Nominal ratings
I Rated current available continuously without overloadability at 40 °C.
P Typical motor power in no-overload use.
Maximum output current
I Maximum output current. Available for 2 seconds at start, then as long as allowed by drive temperature.
Light-overload use
I Continuous current allowing 110% I Ld for 1 minute every 10 minutes at 40 °C.
P Typical motor power in light-overload use.
Heavy-duty use
I Continuous current allowing 150% I Hd for 1 minute every 10 minutes at 40 °C.
Continuous current allowing 130% I Hd for 1 minute every 10 minutes at 40 °C.
Continuous current allowing 125% I Hd for 1 minute every 10 minutes at 40 °C.
P Typical motor power in heavy-duty use.